- Metering Systems
-
Gas Valves
Gas Valves
-
Water Valves and Taps
Water Valves and Taps
-
Metal boxes
- Motorised Valves
- Industrial Ball Valves
Bon Tas
Ball valve for fuel gas with thermic safety device
The Bontas series is a range of valves equipped with a particular thermal safety device which intervenes in case of fire. As soon as the temperature of 100 ° is reached, the device blocks the escape of gas for a minimum of 60 minutes at a temperature of 925°.
The Bontas series ball valves meet the requirements contained in the EN 331 standard and are suitable for systems in accordance with the UNI EN 1775 standard.
The TAS thermal device can be supplied coupled with the ball valve or separately.
Refer to specific national/international standards, where existing, for countries others than Italy.
Material specification
Approved to EN 331
COMPONENT |
MATERIAL |
DESCRIPTION |
||
---|---|---|---|---|
1 | BODY | CW 617 N UNI EN 12165 | FORGED, NICKEL-PLATED | |
2 | TAS DEVICE | MISCELLANEOUS | VARIOUS | |
3 | BALL | CW 614 N UNI EN 12164 | MACHINED, CHROME-PLATED | |
4 | BALL GASKETS | P.T.F.E. | PURE | |
5 | STEM | CW 614 N UNI EN 12164 | MACHINED | |
6 | THRUST WASHER | P.T.F.E. | PURE | |
7 | O-RINGS | ELASTOMER | SUITABLE FOR USE WITH GAS EN549 | |
8 | LEVER HANDLE | ZINC-PLATED STEEL | PVC INSULATED | |
LEVER OR T-HANDLE | AL UNI5076 | PAINTED | ||
9 | SELF-LOCKING NUT | 8G STEEL | ZINC-PLATED |
Characteristics
CHARACTERISTICS | The BON TAS valve is a combination of BON GAS ball valve and the TAS thermic safety device. Rapid on/off 90° turn operation. Gas flow capacity complies with UNI EN 331 standard. |
STANDARDS | The BON TAS ball valve complies with UNI EN 331 and the thermic safety device complies with DIN VP 301. BON TAS ball valve is suitable for installations in conformity with UNI EN 1775. |
HOW THE DEVICE WORKS |
The TAS thermic safety device works in the event of fire as soon as the temperature reaches 100°C, so blocking the fuel gas flow for at least 60 minutes at 925°C temperature. |
END CONNECTIONS | For fuel gas 1^, 2^ e 3^ family 5 MOP. For other uses from PN 80 (1/4”) to PN 16 (size 4”). See pressure/temperature diagram. |
WORKING PRESSURE | For fuel gas 5 MOP. |
TEMPERATURE LIMITS | For fuel gas from -20°C to +60°C. |
TAS Thermic safety device
The TAS thermic safety device works in the event of fire as soon as the temperature reaches 100°C.
Time/temperature diagram
- Light up temperature of fuel gas: approx. 640°C
- BON TAS strength point: 925°C
Download