- Metering Systems
-
Gas Valves
Gas Valves
-
Water Valves and Taps
Water Valves and Taps
-
Metal boxes
- Motorised Valves
- Industrial Ball Valves
Valstop Eurostop
Check valve
Two series of check valves which in common have excellent quality and reduced pressure drops. They are available from ¼” to 4” and can be used with the steel filter as foot valves.
Material specification
COMPONENT |
MATERIAL |
DESCRIPTION |
||
---|---|---|---|---|
1 | BODY | CW 617 N UNI EN 12165 | FORGED | |
2 | END ADAPTER | CW 617 N UNI EN 12165 | FORGED | |
3 |
JUMPER GASKET |
NBR (ART. H0151 - H0153, H0161 - H0163) | MOLDED | |
JUMPER GASKET | FLUOROELASTOMERO (ART. H0141) |
SUITABLE FOR USE WITH WATER | ||
4 | JUMPER | POLYMERIC RESIN | MOLDED | |
5 | JUMPER GUIDE | POLYMERIC RESIN | MOLDED | |
6 | SPRING | STAINLESS STEEL AISI 302 | NORMALIZED |
Characteristics
VALSTOP-EUROSTOP CHECK VALVES | All technical data about VALSTOP check valves (heavy line) are valid for EUROSTOP check valves (standard line) too, except for the pressure/temperature diagram concerning the VALSTOP series. |
END CONNECTIONS | Ends are ISO 228/1 threaded. |
USES (for VALSTOP items H0151- H0153) |
For any type of hydraulic, heating or pneumatic system. For hot and cold water, compressed air, oils. |
USES (for VALSTOP item H0141) | Thanks to its fuoroelastomer gasket (item H0141) VALSTOP is also suitable for applications with non-halogenated hydrocarbons in general (fuels, kerosene etc.). |
INSTALLATION | This valve can be installed in any position (horizontal, vertical, oblique). |
WORKING PRESSURE | Min 0,05 bar with water. Max from PN 40 (1/4”) up to PN 10 (3”). See pressure/temperature diagram. |
MINIMUM OPENING PRESSURE | Min 0,025 bar (25 cm water column). |
MINIMUM TIGHTNESS PRESSURE | Min 0,05 bar (50 cm water column). |
TEMPERATURE LIMITS | Art. H0141 with fluoroelastomer gasket From -15°C to +130°C. Art. H0151/H0161 with NBR gasket From -20°C to +100°C. See pressure/temperature diagram. |
Pressure/temperature diagram
(tested carried with water)
Loss of head diagram
(tested carried with water)
Download
Valstop Eurostop 797.67 KB